FirePro® SoftSeal Coated Strips
Fire stopping penetration seals is crucial for reducing the spread of fire and smoke. ROCKWOOL FirePro® SoftSeal Coated Strips are designed to accommodate structural movement and movement in the services whilst maintaining the fire performance and acoustic properties.
The ROCKWOOL FirePro® SoftSeal Coated Strips are flexible for use in reinstating fire resistance, acoustic and air seal performances in masonry walls, dry wall systems, concrete floors and composite panels, where voids have been created for the passage of services, including pipework and cabling.
ROCKWOOL FirePro® SoftSeal Coated Strips have been tested to BS EN 1366-3 2009 and classified to EN 13501-2, providing up to 2 hours* fire performance (EI120).
*Subject to the application
Specification
NBS Clause | Length (mm) | Width (mm) | *Approved thickness range (mm) |
1200 | 200 | 100 |
*Thickness options may be subject to a minimum production volume. Speak to the specification team for guidance.
Standards and Certification
Testing and classification | EN 1366-3 2009, EN 13501-2 |
CE Marking | CE marked to EAD 350454-00-1104 |
Technical Properties
Fire resistance | Up to 2 hours subject to application |
Density | 80Kg/m3 |
Acoustic performance | Tested to EN 10140 with the following results:
|
Water permeability | Tested to EN 1027 - No leakage observed up to 300Pa. |
Air permeability | Tested to EN 1026 up to 600Pa. Leakage at 50Pa - 0.1/1.4 m³/m²/h. |
CAD Drawings